Budget and Corporate Services Overview and Scrutiny Committee decided this item on Thursday 29 February 2024. Below is the council's own wording, with the papers it was decided on.
RESOLVED : i) That the RAAC Surveys on Council Buildings update report, be received. ii) That the Manager for Asset and Estate Management be requested to provide a written response on which independent school received support from the Council in regard to the identification of RAAC, and whether the Council charged the school for these services. iii) That a RAAC Progress Update standing item be added to this Committee’s agendas going forward, including a tracking matrix of how many buildings had been inspected as well as the outcomes of these inspections. MA&EM / Mayor
Word for word from the decision Bedford published for this meeting.Source: councillorsupport.bedford.gov.uk
Report to Budget and Corporate Services Overview and Scrutiny Committee, 6 pages
Background
Reinforced Autoclaved Aerated Concrete (RAAC) is a lightweight form of concrete that was used in the twentieth century from the mid-1950s to the mid-1980s. The Standing Committee on Structural Safety has noted that “although called ‘concrete’, RAAC is very different from traditional concrete and, because of the way in which it was made, much weaker. The useful life of such (panels) has been estimated to be around 30 years.” (SCOSS Alert, May 2019).
RAAC planks are rectangular in shape and can vary in width from 300 mm to 750 mm, with spans up to 6 m and thicknesses of 100 – 250 mm. The planks are off-white or grey in colour, however various finishes can be applied to the soffits. They are understood to be found in many schools, colleges and hospitals as they were selected commonly for the use of roof decks including wall panels due
5 (1) to their thermal performance (see images below). Following decades of use in the industry, it became apparent that the properties of RAAC meant it contains a lower compressive and tensile strength than normal reinforced concrete, so for a given load, deflection can be ten times greater for an equivalent concrete plank under similar loading conditions (Building Research Establishment, 1996; Built Environment Journal, 2019). In 1982, the production of RAAC in the UK was stopped due to concerns for its structural integrity and life expectancy which was estimated to be around 30 years (Built Environment Journal, 2019). In 1996 the Building Research Establishment published an information paper identifying the various issues associated with RAAC planks that were installed in a school in Essex after just twenty years. A summary of the issues are as follows:
• Panels only have 10 – 20% of the compressive strength of traditional concrete, reducing the shear and bending strength which is exacerbated by water saturation. • Panels have high permeability and are porous with voids forming adjacent to reinforcement, often leading to increase rates of corrosion of the reinforcement. • The reinforcement is less well bonded to the surrounding concrete. • Panels have reduced stiffness characteristics resulting in high displacements, deflections and sagging. • The bearing of the planks onto supporting beams if often insufficient and less than the 75 mm required by modern standards. • There was limited quality control during manufacture and installation so there is a high degree of variability between panels.
Read every report as text, not just the decision
Pro opens the officer report behind each decision, searchable and quotable, across every council we cover.
Follow Budget and Corporate Services Overview and Scrutiny Committee at Bedford and we tell you when its next papers are published, before the meeting rather than after it.
Member Finance Awareness Trainingi) That the briefing note, be noted. ii) That it be agreed that all Councillors be strongly recommended and encourage...
Record of Decisions of the ExecutiveRESOLVED : That it be noted that, as no Executive meetings have been held since the Committee’s last meeting, there w...
We use a cookie to keep you signed in and run your free-paper allowance, and an optional one to count visits. You can accept all, or choose. Privacy & cookies
Necessary
Keeps you signed in and runs your free-paper allowance. Always on.
Always on
Analytics
Counts visits and which pages are used. First-party only, no advertising, never shared.