Housing Scrutiny Sub-Committee, Thursday 16 October 2025 at 6.00pm

HRB Reporting Essential Fire Fighting Equipment Defects Procedure

Noted Scrutiny 3 papers

AI summaryCity of Lincoln Council's Housing Scrutiny Sub-Committee noted the new procedure for reporting essential fire-fighting equipment defects in high-rise residential buildings, required under the Fire Safety (England) Regulations 2023.

AI summaryIn plain English

Written from the decision and the officer reportPDF Pro
OutcomeNotedNo changes made, report received
MoneyNo new costsFunded from existing revenue or capital budgets
What happens nextNot stated
Who it affectsHigh-rise council housing residentsBuildings 7+ floors or 18+ metres tall

What was decided

The Sub-Committee noted the High-Rise Residential Building Reporting Essential Fire-Fighting Equipment Defects Procedure, with thanks.

The procedure is required by the Fire Safety (England) Regulations 2023, which followed Grenfell Tower Inquiry Phase 1 recommendations on lift and equipment defect reporting. Report 3.1, 3.2

The Lincoln Tenants Panel was consulted on 30/09/2025 and accepted the procedure following a briefing session. Report 2.1

Why

The Council, as the Responsible Person, must carry out monthly checks on essential fire-fighting equipment in high-rise buildings and inform Lincolnshire Fire and Rescue Service within 24 hours where defects cannot be resolved. Report 4.1, 6.1

Reporting defects means the Fire and Rescue Service will usually know before arrival if a lift intended for their use is out of service, allowing them to plan accordingly. Report 3.2

The procedure supports the Council's strategic priority to deliver quality housing through routine checks and a clear reporting process. Report 8.1, P22

What happens next

Contractors will undertake routine monthly maintenance visits, with caretakers carrying out daily, weekly or monthly tests as appropriate, and all records kept in the fire logbook. Report 7.1

Where a defect is identified and expected to last more than 24 hours, the Safety Assurance Team will report it to Lincolnshire Fire and Rescue Service using the online form. Report 7.1

Once repairs are completed, the Safety Assurance Team will notify the Fire and Rescue Service that equipment is back in service and any interim arrangements (such as waking watch) will be stood down. Report 7.1

Options considered

  • Chosen: Note the High-Rise Residential Building Reporting Essential Fire-Fighting Equipment Defects Procedure. Recommended in the officer report as the appropriate action for the Sub-Committee Report 11.1

Implications

  • Legal: Non-compliance with legislation is identified as a risk; the procedure ensures compliance with the Fire Safety (England) Regulations 2023 and the Regulatory Reform (Fire Safety) Order 2005. Report 4.3, 10.1, P40
  • Legal: Any procurement related to the procedure will follow PCR2015 or PA23 depending on the route determined. Report P28
  • Equalities: The Public Sector Equality Duty applies, requiring the Council to consider eliminating discrimination, advancing equality of opportunity and fostering good relations. Report P30, P31, P32
  • Staffing: No human resources implications identified. Report P34
  • Other: No land, property or accommodation implications identified; no significant community or environmental impact identified. Report P36, P38

Who and where

  • Residents of City of Lincoln Council high-rise residential buildings (at least 7 floors or 18 metres tall, with at least two residential units) Report 3.3
  • Lincolnshire Fire and Rescue Service (receives defect reports and equipment-back-in-service notifications) Report 7.1
  • Council contractors and caretakers (responsible for checks and repairs) Report 7.1
  • Lincoln Tenants Panel members (consulted on the procedure) Report 2.1

Timeline

  • 30/09/2025: Lincoln Tenants Panel briefing session on the procedure Report 2.1
  • 2025-10-16: Housing Scrutiny Sub-Committee meeting where the procedure was noted
  • Monthly: Routine maintenance visits and checks on essential fire-fighting equipment by contractors and caretakers Report 4.1, 7.1
  • Within 24 hours: Defects that cannot be resolved must be reported to the Fire and Rescue Service as soon as practicable Report 6.1, 4.1

Plain English for the jargon

  • HRB: High-Rise Residential Building: at least 7 floors or 18 metres high, with at least two residential units
  • FRS: Fire and Rescue Service, specifically Lincolnshire Fire and Rescue Service in this context
  • FRA: Fire Risk Assessment, a review of a building's fire risks
  • Responsible Person: The duty-holder under fire safety law, here the City of Lincoln Council as landlord
  • Waking watch: Patrolled fire wardens posted in a building as an interim safety measure when systems are out of service
  • RO: Responsible Officer, the Area Housing Manager in this procedure
  • PCR2015 / PA23: Public Contracts Regulations 2015 and Procurement Act 2023, the procurement legislation frameworks
What was decided, why, and what happens next

Pro reads every officer report for you and explains each decision in plain English: the money, the options, the risks, the timeline, each with the paragraph it came from.

Written by AI from the council's published papers. AI can get things wrong: the council's own wording below is the record.Report a problem
Item50

Resolved

RESOLVED that the report be noted with thanks.
Word for word from the decision Lincoln published for this meeting. Source: democratic.lincoln.gov.uk

Follow this further

Built from Lincoln's papers

What the report saysPro

Report to Housing Scrutiny Sub-Committee

Purpose of report

1.1To update the Housing Scrutiny Sub-Committee on City of Lincoln Council’s (CoLC’s) High-Rise Residential Building -Reporting Essential Fire-Fighting Equipment Defects Procedure.

2. Lincoln Tenants Panel Consultation

2.1Lincoln Tenants Panel (LTP) have been consulted on the procedure, there was a briefing session on 30/09/2025 where members of the LTP were presented the High-Rise Residential Building Reporting Essential Fire-Fighting Equipment Defects Procedure and given the opportunity to ask questions and discuss the content. Any questions were answered, and the procedure was well received and accepted.

Background

3.1The Grenfell Tower Inquiry Phase 1 report findings included that “When the firefighters attended the fire at Grenfell Tower, they were unable to operate the mechanism that should have allowed them to take control of the lifts.” The Inquiry recommended that the owner and manager of every high-rise residential building be required by law to carry out regular inspections of any lifts that are designed to be used by firefighters and to report these results to the Fire and Rescue Service (FRS) at monthly intervals and that they also be required to undertake tests of the mechanism which allows firefighters to take control of the lifts and to inform the Fire and Rescue Service monthly that they have undertaken them.

3.2The Fire Safety (England) Regulations 2023 was implemented and highlights the need to report defects with essential fire-fighting equipment such as lifts, sprinklers, or other fire-fighting facilities that could impact the safety of residents or firefighters. By reporting the defects will help prevent similar situations as the Fire and Rescue Service in the majority of cases will know before arrival that a lift intended for their use in an emergency is out of service and plan accordingly.

3.3The reporting of defects to the firefighting equipment refers to that located at the high-rise residential buildings (HRB) only which are defined as having at least 7 floors or at least 18 metres high and include at least two residential units.

3.4The High-Rise Residential Building - Reporting Essential Fire-Fighting Equipment Defects Procedure is attached as Appendix 1, with full procedure shown including flowchart. 4. Requirement to Check Fire-Fighting Equipment

4.1There is a requirement for the Council as the ‘Responsible Person’ to carry out monthly checks on key fire-fighting equipment and then when required to inform the local Fire and Rescue Service electronically within the 24-hour exception period of defects.

4.2If a defect is found the Council should consider placing signs on/ by the defective lifts and fire-fighting equipment regardless of the time it is expected to take to fix the defects.

4.3The Council should also consider whether the defect would require an update to be made to their building’s fire risk assessment and act accordingly to ensure that they are compliant with their duties under the Regulatory Reform (Fire Safety) Order 2005.

5. Definitions of ‘Essential Fire-Fighting Equipment’

5.1The “essential fire-fighting equipment” includes both equipment provided in buildings to fight fires and important fire safety features and facilities and includes:

• Lifts for use by fire fighters • Evacuation lifts • Inlets for dry-rising mains • Inlets for wet-rising mains • Outlets for dry-rising mains • Outlets for wet-rising mains • Smoke control systems • Suppression systems • Fire detection and fire alarm systems including any detectors linked to ancillary equipment such as smoke control systems (in the common parts) • Evacuation alert systems • Automatic door release mechanisms linked to fire alarm systems

Read every report as text, not just the decision

Pro opens the officer report behind each decision, searchable and quotable, across every council we cover.

Papers for this item

Kept in our archive, download once signed in
PDF
HRB LFRS Fire Fighting Equipment Defects Reporting v. July 2025 Final App AAppendix 349 KB Download
PDF
HRB Reporting Essential Fire Fighting Equipment Defects ProcedureReport 120 KB DownloadRead as text
PDF
Reporting Essential Fire Fighting Equipment Defects FLOWCHART App BAppendix 1.9 MB Download

At this meeting

Whole meeting

Who was there

8 of 13 attended
GH
Councillor Gary HewsonChair, present
PV
Councillor Pat VaughanVice-Chair, apologies
AB
Councillor Alan BriggsCommittee Member, apologies
LB
Councillor Liz BushellCommittee Member, present
NC
Councillor Natasha ChapmanCommittee Member, apologies
LW
Councillor Loraine WoolleyCommittee Member, apologies
MB
Mick Barber (Chair of LTP)Co-Optee, present
CC
Caroline Coyle-Fox (Vice Chair of LTP)Co-Optee, present
MA
Mike Asher (Member of LTP)Co-Optee, apologies
SN
Sean Newton (Member of LTP)Co-Optee, present
DR
Debbie Rousseau (Member of LTP)Co-Optee, present
AP
Councillor Anita PritchardCommittee Member, present

All 13 on the meeting page

On this subject at Lincoln

Search all
  1. HRB Reporting Essential Fire Fighting Equipment Defects ProcedureThis decision
  2. HRB Mandatory Occurrence Reporting ProcedureNoted

More from Lincoln Housing Scrutiny Sub-Committee

All decisions
MeetingDecisionOutcome
17 Aug 2026 Confirmation of Minutes - 4 June 2026RESOLVED that the minutes of the meeting held on 4 June 2026 be confirmed and signed by the Chair as a true record. Decided Open
17 Aug 2026 Lincoln Tenants Panel (LTP) UpdateRESOLVED that: 1. Details of tenant’s contents insurance options from both Marsh and Thistle companies be forwarded t... Noted Open
17 Aug 2026 Financial Performance Quarterly MonitoringRESOLVED that this item be deferred to the next meeting of Housing Scrutiny Sub-Committee to be held on Wednesday 23 ... Deferred Open
17 Aug 2026 Estate Regeneration ProgrammeDecision made – happy with this approach • Projects/Initiatives : • Support to national initiatives • Exploration of ... Decided Open
17 Aug 2026 Tenancy Agreement ProgressRESOLVED that an additional agenda item entitled ‘Summary/Digest Document of Tenancy Agreement Policy’ be added to th... Agreed Open

We use a cookie to keep you signed in and run your free-paper allowance, and an optional one to count visits. You can accept all, or choose. Privacy & cookies