Resolved
Approved with conditions 1 – 7 as set out in the report for the reasons stated in the report and an additional condition 8 as follows: 8. Prior to the installation of the diesel fuel storage tanks and delivery point, full details of the construction of the fuel storage tanks and delivery point that demonstrates: A) that the fuel storage tanks and delivery point are fully containment vessels with an inner tank, which will contain the diesel and an outer tank, which provides security against any loss of containment or leak from the inner tank entering the environment; or B) that any facilities for the storage of oils, fuels or chemicals are sited on impervious bases and surrounded by impervious bund walls, which have a bund capacity of 100% of the total volume for single tanks and in the case of multiple tankage on site 110% of the largest tank or 25% of the total capacity of all the tanks, whichever is the greatest. have been submitted to and approved in writing by the Local Planning Authority. In the case of bunding, all filling points, vents gauges and sight glasses and overflow pipes shall be located within the bund. There shall be no outlet connecting the bund to any drain, sewer, or watercourse or discharging onto the ground. Associated pipework shall be located above ground where possible and protected from accidental damage. The details as approved pursuant to this condition shall be installed prior to the first use of the diesel fuel storage tanks and delivery point and thereafter maintained. Reason: To prevent pollution of watercourses and in compliance with Policy BNE23 of the Medway Local Plan 2013.