Decision The Mayor in consultation with Cabinet agreed to approve capital expenditure up to £520,000 from within the Asset Management capital allocation, subject to pre procurement approval at Mayoral Proceedings and receipt of acceptable tenders. Reasons for the Recommendations Two of the four existing air conditioning units serving the building have already failed and a third has been recommissioned following a recent repair, with no guarantee of the unit remaining operational in the medium to longer term. Air conditioning is required throughout the year to prevent overheating and to maintain a suitable environment for building occupants.
Word for word from the decision Newham published for this meeting.Source: mgov.newham.gov.uk
This report seeks approval to spend capital on the replacement of the air conditioning units serving Building 1000 Dockside to sustain a suitable working environment for both Council operations and commercial tenants within the building.
The Medium Term Budget Strategy agreed by Cabinet in February 2016 included a number of new capital schemes, including a substantial capital allocation for addressing more significant expenditure requirements within the Council’s property portfolio. The Budget Strategy noted that funding for this, and other similar projects, would need to be determined as part of a separate business case.
Approval is now sought to incur capital spend on this project as set out in section 2 of this report.
Executive Summary of Outcomes
Agreement to incur the capital expenditure will support the continued operation of Council functions within an acceptable working environment for staff, visitors and the other commercial tenants within the building.
General Report Template: Ver: 006 Last revised: April 2015 Recommendations
The Mayor in consultation with Cabinet is asked to:
Approve capital expenditure up to £520,000 from within the Asset Management capital allocation, subject to pre procurement approval at Mayoral Proceedings and receipt of acceptable tenders.
Reasons for the recommendations
Two of the four existing air conditioning units serving the building have already failed and a third has been recommissioned following a recent repair, with no guarantee of the unit remaining operational in the medium to longer term.
Air conditioning is required throughout the year to prevent overheating and to maintain a suitable environment for building occupants. Further information is set out within Part B of this report
Name of Lead Officer: Mark Butler Position: Director of Asset Management
Name of Lead Member consulted: Councillor Lester Hudson Position: Deputy Mayor and Cabinet Member for Finance, oneSource, Project Delivery and Commercial Opportunities
Originator of report: Ron Bateman Tel no: 0203 373 0528 E-mail address: [email removed]
Local Government (Access to Information) Act 1985 Background papers used in preparing this report:
Specialist report from KJ Tait Facilities
Copies of Background documents can be obtained from: Ron Bateman Tel no: 0203 373 0528 E-mail address: [email protected]
List of enclosures / Appendices:
Appendix A – Summary of Procurement Options
General Report Template: Ver: 006 Last revised: April 2015 Report - Part A
1. Introduction and Background
1.1The purpose of this report is to seek approval to fund the replacement of the four chiller units at Newham Dockside offices due to recent critical failures of large components including 3 condenser coils and 2 compressors. A separate pre-procurement report is being submitted to Mayoral Proceedings on the same date (16th February 2017) dealing with permissions to undertake a procurement exercise.
1.2The existing chiller units were installed in pairs in 2003, providing air conditioning to the East and West wings of the building, separated by the central atrium area. The specific reason for failure of coils is not known but is assumed to be vibration on long unsupported sections of coils. On the basis of current failures it is considered likely that further coils could fail within the remaining chiller units.
1.3The building is currently operating with 2 of the 4 units functioning which is not sustainable. The air conditioning system is in use throughout the year and due to the thermal efficiency of the building there remains a need to cool the ambient air within each wing, even during winter months.
2. Key Considerations
Read every report as text, not just the decision
Pro opens the officer report behind each decision, searchable and quotable, across every council we cover.
We use a cookie to keep you signed in and run your free-paper allowance, and an optional one to count visits. You can accept all, or choose. Privacy & cookies
Necessary
Keeps you signed in and runs your free-paper allowance. Always on.
Always on
Analytics
Counts visits and which pages are used. First-party only, no advertising, never shared.